    基于时序卷积网络的空冷岛结冰风险预测

    Freezing Risk Prediction of Air-Cooled Island Based on Temporal Convolutional Network

    • 摘要: 针对冬季低温下空冷岛换热管束易局部结冰、威胁机组安全的问题,基于某热电厂空冷岛现场运行数据,提出一种基于时序卷积网络(TCN)的结冰风险预测方法。以环境温度与排汽压力构造结冰风险指数(FRI)并划分四级风险等级,经滑动窗口构造时序样本,建立单步与多步预测模型并与8种模型对比。结果:TCN在370组测试窗口上的风险等级识别准确率为0.976,宏平均召回率为0.919;未来5~60 min多步预测R2由0.990降至0.938。该方法可为空冷岛冬季防冻调控与预警提供支撑。

       

      Abstract: To address the problem that local icing readily occurs in the heat exchange tube bundles of air-cooled islands under low-temperature winter conditions and thereby threatens the safe and stable operation of the unit, a freezing risk prediction method based on a temporal convolutional network (TCN) is proposed using the on-site operation monitoring data of an air-cooled island in a thermal power plant. First, a freezing risk index (FRI) is constructed from the ambient temperature and the exhaust steam pressure, and the continuous FRI is discretized into four risk levels by the thresholds of 20, 50 and 75, whose physical meaning is verified by the equal-risk lines of the index. Fourteen operation variables covering the environmental, meteorological, steam, load, condensate and fan sides are taken as model inputs, and sliding windows of 12 sampling points are used to build time-series supervised samples. A single-step TCN model is then established and compared with ridge regression, random forest, gradient boosting decision tree, extreme gradient boosting, light gradient boosting machine, one-dimensional convolutional neural network, long short-term memory network and gated recurrent unit under identical training, validation and test splits. The results show that the TCN model performs best in both continuous FRI regression and four-level risk identification: on 370 test windows it achieves an accuracy of 0.976, a macro-averaged recall of 0.919, a macro-averaged F1 score of 0.932, an R2 of 0.96 and a MAE of 3.26, and no high-risk sample is misclassified as a no-risk sample. A separately trained multi-step TCN predicts the FRI 5-60 min ahead in a single forward pass, and its R2 decreases from 0.990 at 5 min to 0.938 at 60 min. The proposed method can provide data support for winter anti-freezing regulation and active early warning of air-cooled islands.

       

    /

    返回文章
    返回